RPZ - Reduced Pressure Zone Backflow Assembly
- Only one RPZ required to serve the whole system; (on/off valves can be located downstream of the RPZ)
- RPZ's must be installed a minimum of 12" above ground level.
- RPZ's must be tested by a State-certified Backflow Assembly Tester annually or when moved/repaired.
- In an RPZ equipped system, fertilizer and other agricultural chemicals may be introduced downstream of (after) the RPZ.
- Anti-siphon, anti-backpressure, multi-zone.
- May be installed in hilly terrain.
Check for local installation requirements.
PVB - Pressure Vacuum Breaker
- Only one PVB required to protect the whole system; (on/off valves) can be located downstream of the PVB.
- PVB's must be installed a minimum of 12" above the highest point of water in the ystem.
- PVB's must be tested by a State-certified Backflow Assembly Tester annually or when moved/repaired.
- No chemical or fertilizer can be introduced into an irrigation system protected by PVB's.
- No pumps or sources for backpressure on downstream side of (after) a PVB.
- Anti-siphon, multi-zone.
- Can be pressurized for a full 24 hours.
- Freeze resistant with "FR" feature.
Check for local installation requirements.
AVB - Atmospheric Vacuum Breaker
- One AVB required for each irrigation zone; no (on/off valves) allowed downstream of the AVB.
- Each AVB must be installed a minimum of 6" above the highest point of water in the zone it protects.
- No chemical or fertilizer can be introduced into an irrigation system protected with AVB's.
- No pumps or sources for backpressure on downstream side of an AVB.
- Anti-siphon, single zone.
- Can be only pressurized for a maximum of a 12 hour period out of 24 hours.
Check for local installation requirements.